Input
|
Input type
|
Capacitive humidity sensor & Pt100
|
Operating range of dew point
|
-60 ... +20 dp°C
|
Output
|
Max. scaling range
|
Dew point: -100 ... +20 dp°C
|
Dew point switch to another physical
quantity range
|
Frost point: -60 ... 0
fp°C
Absolute humid. (Volume) 0 ... 50,000 ppm/v
Absolute humid. (Weight) 0 ... 50,000 ppm/w
|
Output signal
|
4 ... 20 mA+RS-485
(Standard)
0 ... 10 V+RS-485 (on request)
|
Signal connection
|
3-wire
|
Linear accuracy
|
-20 ... +20 dp°C : ±1 dp°C
-40 ... -20 dp°C : ±1.5 dp°C
-60 ... -40 dp°C : ±2 dp°C
-70 ... -60 dp°C : ±5 dp°C
-100 ... -70 dp°C : Reference
|
Load resistance
|
Current output : ≦ 500 Ω
Voltage output : ≧ 100 KΩ
|
Output calibrations (ZERO & SPAN)
adjustment range
|
Software
|
Response time t90(Temp. at+25°C)
|
<20 sec
|
Electrical
|
Power supply
|
DC 24 V±15%
|
Current consumption
|
DC 24 V, 50 mA
|
Electrical connection
|
M12 connector
|
Environment
|
Medium
|
Air
|
Operating Temp. for housing
|
-40 ... +60°C
|
Operating Humid. for housing
|
0 ... 95%RH (Non-condensing)
|
Operating Temp. for probe
|
-40 ... +60°C
|
Storage temperature
|
-25 ... +60°C
|
Installation
|
Installation
|
1/2″PT, 1/2″G
|
Protection
|
IP rating
|
IP65 (Probe: IP20)
|
Electrical protection
|
■ Reverse polarity
■ Over-voltage
■ Short-circuit
|
Material
|
Housing
|
S.S.(SUS304)
|
Probe
|
S.S.(SUS304) / SUS sintered filter(SUS316)
|
Weight
|
168 g
|