Input
Signal connection:Capacitive Humidity Sensor & Pt100
Measuring range:Temperature:0 ... 50°C / Humidity:5 ... 95%RH
Recommended measuring range:Temperature::15 ... 35°C / Humidity:20 ... 80%RH
Output
Output:Temperature:RTD(Pt100 / NTC10K), Humidity:0 ... 10 V;4 ... 20 mA
Signal connection:3-wire:Temp. / Humidity:(0 ... 10 V), 2-wire:Humidity:(4 ... 20 mA), 4-wire:Temperature
Temp. influence:0.2%RH/°C
Load resistance:0 ... 10 V;≧ 10 KΩ;4 ... 20 mA / RL<(+V-10) / 0.02<500 Ω
Output calibration(ZERO) adjustment degree:10% of zero-point and full-range
Response time(≧ 1m/s):<20 s
Accuracy
Temperature:±0.3°C+ 0.002°Cx tactual
Humidity(at +25°C):±3%RH(30 ... 70%RH) of F.S.
Humidity(at +15 ... 35°C):±5%RH(20 ... 80%RH) of F.S.
Environment
Measuring medium:Air
Storage temperature:-5 ... +60°C
Max. flow speed: ≦ 15 m/sec
Electrical
Power supply:3-wire:DC 24 V ±20% / 2-wire:DC 9 ... 28 V
Current consumption:0 ... 10 V(3-wire):8 mA / 4 ... 20 mA(2-wire):21 mA
Electric connection:PVC Cable0.32 mm2 x 6C
Installation
Fixed seat:Flange installation
Installation:Probe type
Protection
IP rating:IP24
Electric Protection:■ Polarity reversal protection ■ Over voltage ■ Short circuit
Certification
Certification:CE
Material
Housing:PC fire-proof class(UL94V-2)
Cable:PVC
Weight:17 g(Without cable)
The specifications contained herein are subject to change without notice and any user of said specifications should verify from the manufacturer that the specifications are currently in effect.
Otherwise, the manufacturer assumes no responsibility for the use of specifications which may have been changed and are no longer in effect.
Monitoring for HVAC process / Air conditioning / Environmental ventilation control / Environmental monitoring for building / Factory / Clean / Room / Laboratory / Monitoring for storeroom / Crisper / Agriculture / Food industry / Temperature and humidity measuring in machinery or equipment